EcoFlex Fume Hood Features

Standard –

Our basic package is an upgrade because it lets designers apply Diversity of Operation to reduce HVAC plant size and lifetime costs:

  • Variable Air Volume Controls optimize laboratory airflow.
  • Auto Sash Closers for optimizing safety, air flow management, and energy efficiency.
  • Internal LED Lighting for energy reduction and improved visibility.
  • Waste Handling for smoother operations.

Options –

EcoFlex puts our customers in charge.

  • Schlenk line ergonomically positioned for safety and efficiency.
  • Integrated Fire Extinguisher System from ADX Fire Systems.
  • Storage cabinets options: Flammables Storage Acid Storage General Storage Vacuum Pump Cabinet Drawers
  • Cabinets can be mobile (on casters), suspended, or platform-mounted.
  • Full stainless steel internal lining for Radio Isotope or Perchloric Acid operations.
  • Additional options for electrical and mechanical services available.

Design Parameters –

Operates safely from 60-100 FPM. VAV control with minimum flow achieve 150ACH in the chamber with sash closed.
  • Superstructure dimensions (WHD): 4’-0”, 5’-0”, 6’-0” & 8’-0” width; 36” or 42” depth; 8’-8” height
  • Hood Opening (WH): Working height = 18”, Maximum opening height = 28”
  • Static pressure: 0.25” wg
  • Sash Height: With sash open 18” high the volume flow is:

EcoFlex delivers cost-effective laboratory air-management solutions. With EcoFlex, you get high quality engineering focused on energy savings, safety, and smart ergonomic designs that maximize user satisfaction.

 